Model No.: HLWH-110S ~340S

 
Heating And Cooling Recirculating Air Cooled Water Chiller For Hotel , Office
 
 

 

Heating And Cooling Recirculating Air Cooled Water Chiller For Hotel , Office

 

 

 Model     HLWH

110S

160S

210S

240S

280S

310S

340S

Rated Cooling Capacity

Cooling Capacity (KW)

109

155

208

245

283

307

337

Comp. Input 

Power (KW)

34.7

47.7

63.2

71.2

82.4

89.9

99.9

Rated Heating 

Capacity

Heating 

Capacity (KW)

119

167

224

260

301

326

360

Comp. 

Input Power (KW)

32.6

44.8 

59.6 

67.0 

77.6

84.6 

94.1 

Refrigerant 

R22

Power Supply 

380V/ 3ph/ 50Hz

Safety Protection

Phase reversion protection, 

Phase lack protection, 

Overload current protection,
Discharge air temp.  protection,

 Low & High pressure protection, 

Low temp.  protection, 

Water flow protection.

Number of Refrigeration Circuit

1

Capacity Control (%)

0, 50, 75, 100

Refrigerant Charge (Kg)

30

42

56

68

78

84

93

Air Cooled Heat Exchanger

 Ripple Aluminum 

Fins Around Copper Pipe


Water Cooled Heat Exchanger

Dia.of Pipe (inch)

2-1/2"

3"

3"

3"

4"

4"

4"

Water Side 

Max Pressure  (MPa)

1

Chilled  Water Flow(m3/h)

18.7

26.7

35.7

42.1

48.7

52.7

58.0

Water Pressure Drop (kPa) 

28

33

48

55

61

64

66

Flow of Hot Water(m3/h)

20.4

28.8

38.4

44.7

51.7

56.1

61.9


Axial Fan

Air Flow×1000m3/h

56.8

80.4

113.6

115.2

115.2

160.8

160.8

Power×Qty (KW)

1.2×4

2.0×4

1.2×8

1.2×8

1.2×8

2.0×8

2.0×8

Running Noise dB(A)

75

75

75

75

75

75

75

Total Weight (Kg)

1550

1960

2940

3120

3300

3480

3660

Running Weight(Kg)

1660

2140

3160

3340

3550

3730

3980

 

 

1. Rated Cooling Capacity Based on: DB Temperature 35/WB Temperature 24

   Chilled water inlet/outlet temp. 12/7,  Fouling factor: 0.088.°C/KW.

bigPhoto
 Mr. Aysha

Tel: 86-755-82915708
Contact to this supplier

Related Search

Find more related products in following catalogs on Hisupplier.com

Company Info

Dongguan Golden Refrigeration Equipment Company [China (Mainland)]


Business Type:Manufacturer
City: Shenzhen
Province/State: Guangdong
Country/Region: China (Mainland)

You May Like:

Product (244)