Post Offer Free
Dongguan Golden Refrigeration Equipment Company  

Gold Index: 11929

You are here: home  > Hot Water Air Sourced Heat Pump Air Cooled Chilled Water System

Hot Water Air Sourced Heat Pump Air Cooled Chilled Water System 

Place of Origin: Guangdong, China (Mainland) 
inquire
Add to My Favorites
HiSupplier Escrow
Share |

Product Detail

Model No.: HLWH-360DHM-630DHM

 
Hot Water Air Sourced Heat Pump Air Cooled Chilled Water System
 
 
<tabl

 

Hot Water Air Sourced Heat Pump Air Cooled Chilled Water System

 

 

bigPhoto
 Mr. Aysha

Tel: 86-755-82915708
Contact to this supplier

Related Search

Find more related products in following catalogs on Hisupplier.com

Company Info

Dongguan Golden Refrigeration Equipment Company [China (Mainland)]


Business Type:Manufacturer
City: Shenzhen
Province/State: Guangdong
Country/Region: China (Mainland)

You May Like:

Product (244)

 Model     HLWH

360DHM

390DHM

460DHM

490DHM

540DHM

590DHM

630DHM

Rated Cooling

 Capacity

 Cooling 

Capacity (KW)

358

391

464

490

536

586

632

 Comp. 

Input Power (KW)

116.4

127.6

141.0

148.2

164.8

180.4

197.8

Rated Heating

 Capacity

 Heating 

Capacity (KW)

387

423

491

518

569

622

675

 Comp. 

Input Power (KW)

114.4 

125.6

138.3 

145.4 

161.7 

176.9 

194.4

 Refrigerant 

R407C

 Power Supply 

380V/ 3ph/ 50Hz

 Safety Protection

Phase reversion protection, 

Phase lack protection, 

Overload current protection,
Discharge air temp.  protection, 

Low & High pressure protection, 

Low temp.  protection, 

Water flow protection.

 Number of 

Refrigeration Circuit

2

 Capacity Control (%)

0, 25, 37.5, 50, 62.5, 75, 87.5, 100

  Refrigerant Charge (Kg)

114

122

146

150

164

178

196

 Air Cooled 

Heat Exchanger

Ripple Aluminum Fins Around Copper Pipe

Water Cooled 

Heat Exchanger

 Dia.of Pipe (inch)

5"

5"

3"×2

3"×2

4"×2

4"×2

4"×2

Water Side 

Max Pressure  (MPa)

1

 Chilled  

Water Flow(m3/h)

61.6

67.2

79.8

84.3

92.2

100.8

108.7

 Water 

Pressure Drop (kPa) 

42

54

44

52

54

55

65

 Flow of 

Hot Water(m3/h)

66.6

72.7

84.4

89.1

97.9

107.0

116.1

Axial Fan

Air 

Flow×1000m3/h

172.8

172.8

230.4

230.4

230.4

321.6

321.6

 Power×Qty (KW)

1.2×12

1.2×12

1.2×16

1.2×16

1.2×16

2.0×16

2.0×16

 Running 

Noise dB(A)

75

75

75

75

75

75

75

 Total 

Weight (Kg)

5620

5800

6240

6430

6600

6960

7320

Running 

Weight(Kg)

6040

6280

6680

6850

7100